1 |
Level Transmitter
|
Radar Level transmitter for Fire water tank
Item Specifications: TRANSMITTERS,NO MOD,NO MOD,NO MOD
OUTPUT: 4-20 mA HART (2 nos.) TYPE: Frequency Modulated Continuous Wave (FMCW)
APPLICATION: Fire Water level measurement RANGE: 0 - 12000 (mm) SUPPLY: 120 VAC
Radar Level transmitter for Fire water tank
Location: LM Ahmadi depot, Fire Water tank
Function Level
Transmitter
Measuring
Principle
FMCW
Process Fluid Fire Water
Measuring
Range (mm)
0 - 12000
Process
antenna
8"
Planar Antenna Technology (PAT), Stilling well
Process
Connection
8”, 150# Transmitter Power supply 120 VAC
Transmitter Output 4-20 mA HART (2 nos.)
Internal Diagnostic Required
Cable entries 4 x 3/4" NPT Exd / XP
Write Protection Required
Remote
Display
Required
Display LCD Type, intrinsically
safe
Display Power
supply
Power from
Transmitter
Display Mounting
location
Tank Grade
level
Canopy Yes
Configuration Configurable
via Remote display or remotely via HART communicator
Area
Classification
Zone 1/ ATEX
EExib IIA/IIB T4 Ingress
Protection
IP66/67
Tag plate Yes
Accuracy ±0.5 mm or
better
Housing Material Aluminum
alloy according to EN1706
Features In-built diagnostics, over voltage
protection, Password protected communication via Bluetooth
Certificate Factory
calibration report, material test & conformance certificate.
Warranty 1 Years from
the date of delivery
Commissioning
Assistance
Required
MKR: SIEMENS AG |
Nanometre
|
View
|